TDM Logo

General Controller

Overview 

Produk ini dilengkapi I/O untuk instrumentasi dan aplikasi kontrol sehingga menghasilkan kontrol yang optimal. Sistem tetap dapat dikembangkan saat beroperasi dan mendukung protokol terbuka seperti BACnet/IP, BACnet MS/TP, Modbus™ RTU, serta Modbus™ ASCII.

Features

  • Open communication protocol
  • Connecting various I/Os
  • Flexible software configuration depending on applications
  • Secondary device management
  • Online engineering work
  • Connection to the central monitoring unit
  • Risk distribution
  • Saving space
  • Simple installation

Specification

Item Specification
Power supply Input voltage 100–240 V AC (264 V AC max.)
Input frequency 50/60 Hz ± 3 Hz
Power consumption 45 VA max.
Inrush current 20 A max. (100 V AC)
40 A max. (240 V AC)
Leakage current 0.2 mA max. (100 V AC)
0.5 mA max. (240 V AC)
Insulation resistance Between power terminals together and ground terminal
100 MΩ or higher (500 V DC)
CPU 32-bit
Memory device SDRAM 256 MB, Flash ROM 32 MB, SRAM 2 MB
RAM, RTC backup Powered by lithium batteries (not chargeable)
Communication
– RS-485
Number of channels 2
Communication method BACnet™ MS/TP, Modbus RTU, Modbus ASCII
Communication speed BACnet™ MS/TP: 9.6 kbps, 19.2 kbps, 38.4 kbps, 76.8 kbps
Modbus RTU, Modbus ASCII: 4.8 kbps, 9.6 kbps, 19.2 kbps, 38.4 kbps, 76.8 kbps
Communication distance 1,000 m max.
Number of connectible units For BACnet MS/TP: 50 max./channel
Third-party devices: 31 max./channel
For Modbus RTU, Modbus ASCII: 31 max./channelThere are restrictions depending on the software
– Ethernet Port function Auto-negotiation, Auto-recognition of MDI/MDI-X
Communication method BACnet/IP (IPv4 or IPv6)
Communication speed 100 Mbps
Major material Case, cover Modified PPE resin
DIN holder POM resin
Weight 0.45 kg
Environment
– Operating conditions
Ambient temperature 0–50 °C
Ambient humidity 10–90 % RH (without condensation)
Altitude 2,000 m max.
Vibration 3.2 m/s² max. (at 10–150 Hz)
– Transportation / storage conditions Ambient temperature -20–60 °C
Ambient humidity 5–95 % RH (without condensation)
Vibration (storage) 3.2 m/s² max. (at 10–150 Hz)
Vibration (transportation) 9.8 m/s² max. (at 10–150 Hz)
– Others • No corrosive gas should be detected.
• The product should not be exposed to direct sunlight.
• Do not let the product get wet.
Installation location In the control panel
Installation method Installed on a DIN rail or with screws