Data logger berakurasi tinggi dan mudah dipasang yang dirancang untuk mengukur serta merekam konsumsi daya dan energi pada beban colokan 120V. Perangkat ini cukup digunakan dengan mencolokkan peralatan kantor, mesin penjual otomatis (vending machine), atau perangkat listrik lainnya langsung ke data logger.
Akurasi pengukuran 0,5%
Mode Meter untuk pemantauan real-time
Data bertanda waktu dan terakumulasi
Kapasitas memori besar
Backup baterai internal
Layar LCD lengkap dan informatif
Kompatibel dengan HOBOware & HOBOware Pro
Note: The UX120-018 logger is intended for use on 15 AMP circuits (NEMA 5-15P) with a working voltage of 120V AC ±10% at 50/60Hz and a max power of 1800W.
| RMS Voltage Accuracy | ±0.5% up to 14 A continuous; ±1.0% over 14 A at 100% duty cycle |
|---|---|
| RMS Current Accuracy | ±0.5% up to 14 A continuous; ±1.0% over 14 A at 100% duty cycle |
| Active Power Accuracy | ±0.5% up to 14 A continuous; ±1.0% over 14 A at 100% duty cycle |
| Active Energy Accuracy | ±0.5% up to 14 A continuous; ±1.0% over 14 A at 100% duty cycle |
| Power Factor Accuracy | ±0.02 |
| Drift | Up to 0.5% typical within 1 year |
| Resolution | Voltage (RMS): 10 mV Amps (RMS): 0.1 mA Active Power: 10mW down to 1 watt loads @ 120VAC Active Energy: 10 mW Apparent Power: 10 mVA Power Factor: 0.01 PF |
| Operating Environment | Logging: 5°C to 40°C (41°F to 104°F) Humidity: 0–95% RH (non-condensing) Altitude: up to 2,000 m (6,562 ft) |
| Operating Modes | Meter or logging when launched with HOBOware |
| Logging Rate | 1 second to 18 hours, 12 minutes, 15 seconds |
| Statistics Sampling Rate | 60 Hz or 16.67 ms (single-cycle) |
| Memory Modes | Wrap when full or stop when full |
| Start Modes | Immediate, push button, date & time, or next interval |
| Stop Modes | When memory full, push button, or date & time |
| Restart Mode | Push button |
| Time Accuracy | ±1 minute per month at 25°C (77°F), see Plot A |
| Power Source | Line-powered with 0.92 m (3 ft) AC power cord or two AAA 1.5 V alkaline batteries (user replaceable) |
| Battery Life | 2 years with line power 6 months battery only (no line power) with logging rate of 1 minute or greater operating at 25°C (77°F) |
| Memory Capacity | 4 MB (1.4 million measurements, maximum) |
| Download Type | USB 2.0 interface |
| Full Memory Download Time | Approximately 1.5 minutes |
| LCD | LCD is visible from 0° to 50°C (32° to 122°F); the LCD may react slowly or go blank in temperatures outside this range |
| Size | 13.97 × 7.62 × 4.75 cm (5.5 × 3 × 1.87 in) |
| Weight | 230.8 g (8.14 oz) |
| Ratings | IP50
|
| Calibration | This device has been calibrated using equipment that has been tested in accordance with ANSI C12.20 0.5%. |
| Plot A |